GDJB-II Secondary Injection Test Set
A. Kondisi kerja
1. Sumber daya: AC 220V±10%,50Hz
2. Lingkungan kerja: Suhu -10 ℃ ~ 40 ℃;Kelembapan: ≤85%
3. Suasana: 86-106kPa
B. sumber daya Output
1. tegangan AC: 0-220V / 3A Luwes
2. AC saiki: 0-100A / 7V (200A bisa disesuaikan);0-20A / 25V Luwes;0-5A / 5V Bisa diatur
3. voltase DC: 0-220V / 3A Luwes
4. DC saiki: 0-20A / 25V
5. Output tegangan tetep: DC 24V/48V/110V/220V
6. Akurasi saiki / Tegangan: ± 1%.
C. Indeks Prestasi
1. Ammeter lan voltmeter: 41/2 digit.
2. Digital millisecond meter: 0-99.9999s(999.999s bisa disesuaikan) Resolusi: 0.1ms.
D. Fungsi
1. Measure relay: Ngukur nilai wiwitan, nilai bali lan drop-off kanggo rasio pick-up arus, relay voltase.
2. Relay wektu: Ngukur nilai wiwitan, nilai bali lan wektu tumindak.
3. Relay penengah: Ukur kabeh jinis kumparan kanthi wiwitan.Nilai wiwitan tetep, nilai bali, nilai ditahan lan wektu tumindak relay intermediate coil.
4. Reclosing relay: Tes daya kapasitansi, wektu ngisi, wektu reclosing lan tes komponen tengah.
5. Relay diferensial: Tes Eksitasi DC, Tes rem, Tes karakteristik Volt-ampere.
6. relay umum liyane lan LV circuit breaker.
jeneng | Qty |
Set tes injeksi sekunder GDJB-II | 1 pc |
Kabel daya | 1 pc |
Garis tes | 6 pc |
Cbaris saiki | 2 pc |
Sekring | 4 pc |
Manual | 1 salinan |
Sertifikat | 1 salinan |