GDFJ-311M SF6 Gas Dekomposisi Product Tester
GDFJ-311M SF6 Gas Decomposition Product Tester minangka piranti portabel sing dirancang kanggo ngukur produk dekomposisi gas SF6.Komponen inti kanthi sensor elektrokimia saka Membrapor kanggo nguji produk dekomposisi gas SF6.Kajaba iku, kita uga nggunakake chip hardware profesional lan algoritma piranti lunak STMicroelectronics sing apik banget.
Analisis produk dekomposisi peralatan listrik terisolasi gas SF6
Deteksi kualitas gas SF6 daur ulang
R&D nggunakake
DL/T 639-1997: Safety and Protection Guide for Operation Test and Maintenance Personnel of SF6 Electrical Equipment.
Guodian No.72 Annex 3 [1999] Ukuran kanggo Pengawasan Kualitas lan Manajemen Switchgear Tegangan Tinggi.
GB / T 17626: Kompatibilitas elektro-magnetik - Testing lan Techniques Takeran.
GB/T 2423: Tes Lingkungan Produk Listrik lan Elektronik.
DL / T596: Kode Test Nyegah kanggo Peralatan Listrik.
GB / T 6388: Tandha Pengiriman Paket Transportasi.
GB/T 18867-2014: Gas kanggo Industri Elektronik—Sulfur Hexaflouride.
GB / T8905: Pandhuan kanggo Manajemen lan Ngukur Gas SF6 ing Peralatan Listrik.
Metode pangukuran | Prinsip pangukuran elektrokimia (kanthi sensor saka Membrapor) |
Suhu sekitar | -20 ℃ ~ +60 ℃ |
Range pangukuran | SO2: 0~200PPmv, H2S: 0~200PPmv CO: 0~500PPmv, HF: 0~50PPmv |
Kesalahan | SO2: <10PPmv, ±0.3PPmv;> 10PPmv, ± 3% H2S: <10PPmv, ±0.3PPmv;> 10PPmv, ± 3% CO: <50PPmv, ±2PPmv;>50PPmv, ±4% HF: <10PPmv, ±0.3PPmv;> 10PPmv, ± 3% |
Baleni-kemampuan | SO2: <10PPmv, ± 0,2PPmv;> 10PPmv, ± 2% H2S: <10PPmv, ±0.2PPmv;> 10PPmv, ± 2% CO: <50PPmv, ±2PPmv;>50PPmv, ±2% HF: <10PPmv, ±0.2PPmv;> 10PPmv, ± 2% |
Resolusi | 0.1PPmv |
Unit tampilan | PPmv |
Aliran gas | 200 ~ 300ml / min |
Tampilan aliran gas | 0 ~ 1000mL impor digital gas flow meter |
tekanan gas | ≤1MPa |
Kelembapan | 90% RH |
Pengaruh nilai pangukuran | Ora ana pengaruh tekanan lan aliran |
sumber daya | 220VAC±10%, 50Hz, AC/DC nggunakake, terus digunakake luwih saka 8 jam. |
Ukuran | 395 * 295 * 155 mm |
Bobot | 2 kg |
Unit utama | 1 atur |
Pipa Teflon (kalebu katup pangaturan aliran lan konektor cepet) | 1 atur |
Pipa gas | 1 atur |
spare part | 1 atur |
Pandhuan pangguna | 1 salinan |
kertu babar pisan | 1 salinan |
Laporan tes pabrik | 1 salinan |
Pangisi daya | 1 pc |